Building and approvals

Building Code of Pakistan fire safety for shop, office and clinic fit-outs: what the 2016 Provisions ask

Published · 10 min read · RN Tech Associates · in Building and approvals

Short answer

The Building Code of Pakistan Fire Safety Provisions 2016 apply to fit-outs as well as new buildings: clause 1.3.6.3 says renovations, alterations and changes of occupancy must conform. For a shop, office or clinic that means two exits within 30 m travel, doors at least 810 mm clear that open without a key, Class A or B finishes in exit routes, emergency lighting, extinguishers within 22.9 m, and alarms or sprinklers above set sizes.

Building Code of Pakistan fire safety for shop, office and clinic fit-outs: what the 2016 Provisions ask

Key points

  • The 2016 Provisions were made binding on engineering work by S.R.O. 1073(I)/2016 and 1074(I)/2016 and apply to new and existing buildings; a fit-out or change of use must conform (clause 1.3.6.3).
  • Classify the space first: a shop is mercantile, an office is business, and a clinic depends on whether patients stay; the authority rules on doubtful cases.
  • Every storey or part of one needs at least two exits, with travel distance up to 30 m for shops and offices (45 m if fully sprinklered).
  • Extinguishers are required in every occupancy except one and two family houses, with no point more than 22.9 m (75 ft) from one.
  • In Islamabad, CDA's Building Control Regulations require the 2016 Provisions, and its 2010 fire regulations allow fines of up to Rs. 500,000.

The code, and why a fit-out has to meet it

The Building Code of Pakistan Fire Safety Provisions 2016 is the national fire code for buildings. The Pakistan Engineering Council (PEC) prepared it with the National Disaster Management Authority, benchmarked against the US NFPA 1 Fire Code 2015. Two notifications of 31 October 2016, S.R.O. 1073(I)/2016 and 1074(I)/2016, published in the Gazette on 22 November 2016, added it to PEC’s bye-laws for engineering works and for consulting engineers. They say three things a fit-out owner needs to know:

  • Construction and modification of buildings in violation of the Provisions is a violation of professional engineering work under the PEC Act.
  • The bye-law applies to new and existing buildings. Existing buildings had three years from notification to comply, and one year for the minimum: fire alarm and detection, extinguishers, emergency response plans and fire drills.
  • Enforcement rests with the “Authority Having Jurisdiction” (AHJ): development authorities, district, tehsil and municipal administrations, cantonments and others, each within its own area.

The code then closes the gap most tenants assume is there. Clause 1.3.6.3: “Repairs, renovations, alterations, reconstruction, change of occupancy, and additions to buildings shall conform to these Provisions.” A plaza that was approved years ago does not make your new partitions, ceiling and shutter compliant. A house or flat turned into an office or clinic is a change of occupancy.

First, classify the space

Almost every number in the code depends on the occupancy class (Chapter 5). For fit-outs, four matter:

Your space Occupancy class Definition in the code
Shop, showroom, pharmacy, salon selling products Mercantile (5.1.9) Display and sale of merchandise
Office, bank branch, consultancy, day clinic (see below) Business (5.1.10) Transaction of business other than mercantile
Restaurant, cafe, hall, gym with 50 or more people Assembly (5.1.2) Gathering of 50 or more persons
Hospital, clinic keeping four or more patients Health care (5.1.5) Treatment or care of four or more patients

Clinics are where the code is unclear. Chapter 5 defines health care as treatment of four or more patients “simultaneously”. Chapter 3 (3.3.157.10) adds “on an inpatient basis”, for patients mostly incapable of self-preservation. A walk-in GP, dental or physiotherapy clinic therefore usually sits with business, and the finish table groups “Business and Ambulatory Health Care” together. Clause 5.1.1.1 gives the authority the final word where classification is in question, so settle it before the layout is drawn.

Then work out the occupant load: floor area divided by the factor in Table 10.10.2.1. Offices are 9.3 square metres per person; a shop’s sales floor at street level is 2.8, and 5.6 on upper floors; outpatient health care is 13. A 200 square metre office is designed for 22 people; a 100 square metre ground-floor shop for 36. That number sets exit widths, alarm thresholds and drill duties.

Where shops and offices share a building, each part is classified by its use and the building meets the most restrictive requirements, unless the occupancies are separated by 2-hour fire-rated construction (1 hour if sprinklered). A small area under 10% of the main occupancy’s area may be treated as part of it (5.1.13).

Exits, doors and corridors

Exits are where fit-outs most often go wrong, because partitions, counters, shutters and access control all sit on the escape route.

Requirement Clause What it means on site
At least two means of egress from every storey or portion 10.11.2 A deep shop or office with one door at the front needs a second way out
Travel distance to an exit: 30 m for business and mercantile Table 10.11.1 Up to 45 m if the building is fully sprinklered
Dead-end corridors no longer than half the travel distance 10.12.2.2 No long cul-de-sac behind the stock room
Two exits at least half the area’s diagonal apart (a third if sprinklered) 10.12.4.2 to 10.12.4.3 Two doors side by side count as one
Door clear width at least 810 mm 10.9.1.4.2 Measured with the door open at 90 degrees
Side-hinged or pivoted doors, swinging in the direction of exit 10.9.1.5 Sliding or rolling doors only for business areas of 10 people or fewer
Openable from inside without a key, tool or special knowledge 10.9.1.8.1 to 10.9.1.8.2 No padlock inside while the space is occupied
Corridor at least 1,200 mm clear where 50 or more people use it 10.10.2.5.2 915 mm minimum width for other egress routes
Exit access not through kitchens, store rooms, toilets or lockable rooms 10.12.5.1 The fire exit cannot be through the stock room

Three details catch fit-outs out. Rolling security shutters and grilles on an exit are allowed only in existing occupancies, fully open during business hours, with the sign the code prescribes (10.9.1.5.3). Electrically locked and access-controlled doors must release on loss of power, open with one hand, and have a “PUSH TO EXIT” release 1,015 to 1,220 mm above the floor and within 1,525 mm of the door, unlocking automatically when the alarm or sprinklers operate (10.9.1.8.4 and 10.9.1.8.9). And mirrors may not be placed on exit doors, nor curtains hung over them (10.8.2.2, 10.12.5.3).

Table 10.9.1.8.13 also lists door fire ratings by location, among them an office main entrance at 60 minutes, smoke-proof and self-closing, and exit corridor doors at 60 minutes. A frameless glass office entrance off a common corridor needs that question answered by the building’s engineer before it is ordered. Stairways may not hold gas piping or electrical panels (10.16.4).

Finishes, furniture and signs

Interior finish is where interior design and fire safety meet. Wall and ceiling finishes are classed by flame spread index under ASTM E 84 or UL 723 (8.4.4.3): Class A is 0 to 25, Class B 26 to 75, Class C 76 to 200, all with a smoke developed index up to 450. Partitions, panelling and wall pads count as interior finish, not furniture (8.4.2.5).

Occupancy (Table 8.4.3.1) Exits Exit access corridors Other spaces
Business and ambulatory health care A or B A or B A, B or C
Mercantile A or B A or B A or B
Health care A A (B on lower part) A (B in small rooms)
Assembly, 300 people or fewer A A or B A, B or C

Two cautions. For shops the table says A or B everywhere, while clause 14.12.3.2 allows A, B or C for new wall and ceiling finish; specifying A or B satisfies both. And textile wall and ceiling coverings and expanded vinyl must meet Class A, while foamed plastics are allowed as finish only if the authority approves (8.4.5). Health care occupancies of one or two storeys are exempt from the finish rules (14.4.1.2). Posters and paper on walls may cover no more than 20% of the wall area (8.4.2.7.1).

Exits need an approved sign readable from any direction of approach, with no point in an exit access corridor more than 30 m from a sign (10.15). Emergency lighting must come on within 1 second of a power failure, give at least 10 lux on the centreline of the escape route at floor level, run for at least 1 hour 30 minutes, and be tested monthly for 30 seconds and yearly for 1.5 hours if battery powered (10.14).

Extinguishers, alarms and sprinklers

What a fit-out must provide depends on the occupancy and the size of the space or building.

System Shop (mercantile) Office or day clinic (business) Clause
Portable extinguishers Always; at least 2-A rating; within 22.9 m travel Always; same rule 9.6.1.2, Table 9.6.3.2.1.1
Fire alarm and detection Class A mercantile: over 2,800 square metres or more than three sales storeys Three or more storeys, or 50 or more people above or below the exit level, or 300 or more in total (new) 9.7.2.21, 9.7.2.23
Automatic sprinklers New shops of three or more storeys or over 1,115 square metres; sales basements over 232 square metres No general threshold; required if the building is high-rise 9.3.2.20, 9.3.2.23
Any building Basements over 232 square metres (new); high-rise (over 18 m with lifts) also needs a voice alarm Same 9.3.2.2, 3.3.25.6, 9.7.2.27

Extinguishers weighing up to 18.14 kg are mounted with the top no more than 1.53 m above the floor and the bottom at least 102 mm clear of it, in plain view along the normal path of travel (9.6.3.1.3). Choose the type for the hazard: Class K for commercial cooking, and units listed for Class C for server and electronic rooms, where dry chemical units are not to be used (9.6.2.5). Staff in shops and offices must be periodically trained in using them (14.12.2.3, 14.13.2.3).

If the building already has sprinklers or detectors, the fit-out must keep them working: new partitions and ceilings change coverage, so the system’s designer has to check the layout. The authority may require construction documents and a permit before any fire protection system is installed or modified (9.1.1).

During the works

Chapter 11 covers alterations as well as new construction. The owner names one person responsible for fire prevention on site; combustible waste and debris go out daily; oily rags go in an approved container; an extinguisher sits at each usable stairway on every floor once combustible material accumulates; and “temporary protective coverings used on fire protection devices during renovations, such as painting, shall be removed promptly” (11.3.2.3.5), so check every detector head at hand-over. If a fire protection system is out of service for more than 4 hours in 24, a fire watch is required (9.1.8).

Who enforces it in Islamabad and Rawalpindi

Islamabad. Clause 4.1.18 of CDA’s Building Control Regulations 2020, as amended by S.R.O. 1074(I)/2023, says the 2016 Provisions “shall be followed”, that fire safety drawings and certification must follow them, and that installed fire safety equipment must be certified by the relevant authority every year, with the certificate posted in the building. The older Islamabad Fire Prevention and Life Safety Regulations 2010 (S.R.O. 70(I)/2011) remain on CDA’s list: they let CDA’s nominated officer inspect after three hours’ notice (regulation 3), require fire and life safety clearance for new buildings at plan approval and again at the completion certificate (4(3); for a house, see the CDA completion certificate guide), and set fines of up to Rs. 500,000, plus up to Rs. 3,000 a day for a continuing offence (9). On 30 August 2026 CDA said its Fire and Emergency Services Directorate had sealed five buildings and fined three hospitals for failing fire and life safety observations.

Rawalpindi. The authority depends on where the premises are: the development authority, the municipal administration or a cantonment board, all of which are named as AHJs in the 2016 bye-law. Ask the one for your building which documents it wants for a fit-out before work starts.

A fit-out checklist

  1. Classify the occupancy and compute the occupant load from the measured floor area.
  2. Draw both exits, the travel distances and the door swings on the layout before choosing finishes.
  3. Check every shutter, glass door and access-controlled door against clauses 10.9.1.5 and 10.9.1.8.
  4. Specify finishes by class, with test evidence for textiles, vinyl, foam and panelling.
  5. Place exit signs, emergency lighting and extinguishers on the drawings, not on site.
  6. Ask the building’s engineer whether alarm or sprinkler coverage changes with your layout.
  7. Name the person responsible for fire safety during the works, and uncover detectors at hand-over.

Our interior design work starts from a measured plan of the existing space and draws the escape routes, door hardware and finish classes into the layout and schedules, so the fit-out contractor builds them in rather than adding them after inspection. For an existing unit with no drawings, an as-built survey gives that plan. If you are agreeing a fit-out contract, our guide to what a construction contract should say applies to shops and offices too, and the structural side of the same CDA regulations is explained in our guide to the seismic zone of Islamabad and Rawalpindi. The work itself can be checked against the drawings through project supervision. To plan a shop, office or clinic fit-out, send the unit’s location, area and intended use through our contact page.

Want RN Tech Associates to handle this for your site?

Send the location and what the work is for. We reply with the questions that decide scope and price.

Questions

Common questions

01Does the Building Code of Pakistan fire safety apply to my shop in an existing plaza?

Yes. The bye-law notified in 2016 applies to new and existing buildings, and clause 1.3.6.3 says renovations, alterations and changes of occupancy must conform. Existing buildings were given three years from notification to comply, and one year for the minimum measures: alarm and detection, extinguishers, emergency plans and drills.

02How many fire extinguishers does a shop or office need?

Under Table 9.6.3.2.1.1, each extinguisher for ordinary combustibles must be rated at least 2-A, cover no more than 3,000 sq ft per A unit in a light hazard space (11,250 sq ft at most per extinguisher), and no point may be more than 75 ft (22.9 m) from one. Even a small unit needs at least one. Kitchens need Class K units and delicate electronics need units listed for Class C, not dry chemical.

03Does an office need sprinklers in Pakistan?

The 2016 Provisions do not set a general sprinkler threshold for offices. Sprinklers are required in high-rise buildings (taller than 18 m with lifts), in basements over 232 square metres in new buildings, and in new shops of three or more storeys or over 1,115 square metres. An office does need a fire alarm and detection system if the building has three or more storeys or the office holds 300 people or 50 above or below the exit level.

04Is a clinic a health care occupancy under the code?

It depends on the patients. Chapter 5 defines health care as treatment of four or more patients at the same time, but the Chapter 3 definition limits it to inpatients mostly incapable of saving themselves. A day clinic where patients walk in and out is usually treated as a business occupancy, which the finish table groups with ambulatory health care. Clause 5.1.1.1 leaves doubtful cases to the authority, so confirm the classification before the design is fixed.

05Do I need a fire NOC for a commercial fit-out in Islamabad?

For new buildings, regulation 4(3) of the Islamabad Fire Prevention and Life Safety Regulations 2010 requires clearance from CDA's emergency directorate at building plan approval and again at the completion certificate. CDA's Building Control Regulations also require fire safety drawings and certification to follow the 2016 Provisions and installed equipment to be certified every year. Ask CDA's Fire and Emergency Services Directorate what it needs for your fit-out.

06Can I keep a rolling shutter on my shop's only door?

Only in an existing occupancy and only if it stays fully open while the shop is open to the public, is operable from either side without special effort, and carries the sign "THIS DOOR TO REMAIN OPEN WHEN THE SPACE IS OCCUPIED" (clause 10.9.1.5.3). New exit doors are side-hinged and swing in the direction of exit travel.

→Request a survey